Bill Text: TX HB3314 | 2025-2026 | 89th Legislature | Introduced


Bill Title: Relating to certain energy efficiency performance standards for residential construction.

Spectrum: Partisan Bill (Republican 1-0)

Status: (Introduced) 2025-02-25 - Filed [HB3314 Detail]

Download: Texas-2025-HB3314-Introduced.html
  89R958 MP-D
 
  By: Harris H.B. No. 3314
 
 
 
A BILL TO BE ENTITLED
 
AN ACT
  relating to certain energy efficiency performance standards for
  residential construction.
         BE IT ENACTED BY THE LEGISLATURE OF THE STATE OF TEXAS:
         SECTION 1.  Chapter 388, Health and Safety Code, is amended
  by adding Section 388.0045 to read as follows:
         Sec. 388.0045.  RESIDENTIAL BUILDING ENERGY EFFICIENCY
  PERFORMANCE STANDARDS FOR ATTIC AND RAFTER ASSEMBLIES. (a) This
  section applies only to residential construction. 
         (b)  Notwithstanding any requirement contained in an energy
  code adopted under Section 388.003(a) or (b), or a local amendment
  adopted under Section 388.003(d), pertaining to the insulation of
  unvented attic or unvented enclosed rafter assemblies, a local
  jurisdiction shall consider an unvented attic or unvented enclosed
  rafter assembly to be in compliance with the requirements of the
  portion of the energy code administered and enforced by that local
  jurisdiction pertaining to the insulation of unvented attic or
  unvented enclosed rafter assemblies if:
               (1)  the attic or rafter assembly is insulated and air
  sealed with air impermeable insulation to an R-value of at least:
                     (A)  20 if the attic or rafter assembly is located
  in climate zone 2 or 3; or
                     (B)  26 if the attic or rafter assembly is located
  in climate zone 4; and
               (2)  the building in which the attic or rafter assembly
  is located:
                     (A)  attains a blower door test result of less
  than 3.0 ACH50;
                     (B)  has a mechanical ventilation system that does
  not rely solely on a negative pressure strategy;
                     (C)  if insulation is installed below the roof
  deck and the exposed portion of the roof rafters is not already
  covered by air impermeable insulation to an R-value of at least 20
  or 26, as applicable, has the exposed portion of the roof rafters
  wrapped in insulation to an R-value of at least 3, except that the
  rafters are not required to be covered by insulation if:
                           (i)  the rafters are directly covered by
  drywall or finished ceiling; or
                           (ii)  continuous insulation is installed
  above the roof deck; and
                     (D)  contains inside the building's thermal
  envelope the building's indoor heating, cooling, and ventilation
  equipment, including ductwork.
         SECTION 2.  This Act takes effect September 1, 2025.